# 48369K005 Page 1Save these instructions for future referenceINSTALLATION ANDMAINTENANCE INSTRUCTIONS(2,4)SH13 SeriesSelf-Contained Heat PumpImproper
Page 10 # 48369K005Owner RecordModel # _________________________________Serial # _________________________________Installation Date __________________
# 48369K005 Page 11Figure 9Wiring DiagramP/N 48349-001208/230V-1-60GW1CROBLKREDYELREDCONTACTORTHERMOSTATHIGH PRESSURESWITCH(IF USED)L1T1T2L2CHFCONDENS
Page 12 # 48369K005Limited WarrantyAugust 1, 1997This warranty gives you specific legal rights and you may have other rightswhich vary from state/prov
Page 2 # 48369K005INSTALLATIONThese instructions explain the recommended method ofinstallation of the SH heat pump unit and associatedelectrical wirin
# 48369K005 Page 3Roof Curb AssemblyFigure 2Table 1Roof Curb InstallationIf a roof curb is used, follow the manufacturer’s InstallationInstructions an
Page 4 # 48369K005Figure 4Removing Bottom Duct CoversBase1. Remove screw and lift.2. Slide cover to free back pin.12When fastening ductwork to side du
# 48369K005 Page 5When connecting electrical power and controlwiring to the unit, waterproof type connectorsmust be used so that water or moisture can
Page 6 # 48369K005ThermostatThe room thermostat should be located on an inside wallwhere it will not be subject to drafts, sun exposure, or heatfrom e
# 48369K005 Page 7OPERATIONSequence of OperationCoolingWhen the thermostat is in the cooling mode, the O circuit ispowered which energizes the reversi
Page 8 # 48369K005the timing selector jumper is not in place, the controldefaults to a 90-minute defrost interval. The maximumdefrost period is 14 min
# 48369K005 Page 9Cooling System PerformanceFor maximum performance of the cooling system, operat-ing temperatures and pressure should be checked.Subc